No Cool Troubleshooting

3-WAY VALVE CENTERING PROCEDURE

Place the 3-Way Valve in “Home / Fully Open” Position

OPTION 1

One method to center the 3-way valve is to put the unit into Test Mode One. Press the Test Button on the Main board one time and wait approximately 15 seconds then unplug the unit. The 3-Way Valve will be fully open at this point.

Test Button on Main PCB:

OPTION 2

Another method to center the 3-way valve is to use the 3-Way Valve jig (part number CJT30120301) and the 3-Way valve cable included with the jig. With this tool you will be able to center the 3-way valve as shown in the instructions below.

Connect the battery to the jig:

Connect the jig to the 3-Way Valve:

Activate the 3-Way Valve with the number one button:

Select the 3-Way Valve Type:

Select “All”, this will open the 3-Way Valve to both evaporators making evacuation and charging faster: